Buffer Cleaner
Oman Chemical is leading one Largest Supplier, Manufacture a
It is a well - balanced blend for boiler water treatment products, resulting in a scale and corrosion control by one shot operation. A unique one-step Boiler treatment liquid to control the formation of rust and scale in low pressure and auxillary boilers with working pressure up to 20 bars.
Control is by simple boiler water tests or RX CLEANSERS can provide a suitable test kits for this purpose.
Used in low pressure and auxillary boilers
:::::::::::::::::::::Alkalinity TEST FOR BOILER & COOLING WATER ::::::::::::::::::::::::
REAGENT & APPARATUS :
Reagent: RXSOL TK 7 , TK 8 , TK 9 , . Apparatus : TEST TUBE , Titrator or DROPPER
PROCEDURE for p-ALKALINITY test ( STEP WISE ):
RESULT : Each DROPS is equivalent to 25 PPM of Alkalinity .
NOTE : p-Alkalinity VALUE = 25 X ( Total Number of DROPS of TK9 , during 3rdstep )
PROCEDURE for p-ALKALINITY & TOTAL ALKALINITY ( STEP WISE ):
RESULT : Each DROPS is equivalent to 25 PPM of Alkalinity .
NOTE : p-Alkalinity ppm CaCO3VALUE ( A ) = 25 X ( Total Number of DROPS of TK9 , during 3rdstep )
Total Alkalinity ppm CaCO3VALUE = A + { 25 X ( Total Number of DROPS of TK9 , during 5th step )}
NUMBER OF DROPS OF TK9 p-Alkalinity as CaCO3
1 >>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>25
3 >>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>> 75
5 >>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>> > 125
20 >>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>> > 500
40 >>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>> 1000
Optimum Result : p-Alkalinity level is between 100 to 150 PPM is suggested. For Below 50 ppm , Dose ½ Ltrs of RXSOL-50-5001-020for 1000 Ltrs of BOILER WATER , to maintain p-Alkalinity level 100 ppm. Refill pack : REPLACEMENTS TK7 : ECONOMIC PACK ( 100 / 200 / 500 ml ) available TK8 : ECONOMIC PACK ( 100 / 200 / 500 ml ) available TK9 : ECONOMIC PACK ( 100 / 200 / 500 ml ) available |
For Tank cleaning operation pl. click here to know more................
OTHER VALUABLE PRODUCTS
CHARACTERISTIC :
Basic Boiler System Schematic
Below is a summary of problems associated with the common impurities in water and solutions to each problem.
List Of Problems Caused By Impurities In Water
Impurity (Chemical Formula) |
Problems |
Common Chemical Treatment Methods |
Alkalinity (HCO3-, CO32- and CaCO3) |
Carryover of feedwater into steam, produce CO2 in steam leading to formation of carbonic acid (acid attack) |
Neutralizing amines, filming amines, combination of both, and lime-soda. |
Hardness (calcium and magnesium salts, CaCO3) |
Primary source of scale in heat exchange equipment |
Lime softening, phosphate, chelates and polymers |
Iron (Fe3+ and Fe2+) |
Causes boiler and water line deposits |
Phosphate, chelates and polymers |
Oxygen (O2) |
Corrosion of water lines, boiler, return lines, heat exchanger equipments, etc. (oxygen attack) |
Oxygen scavengers, filming amines and deaeration |
pH |
Corrosion occurs when pH drops below 8.5 |
pH can be lowered by addition of acids and increased by addition of alkalies |
Hydrogen Sulfide (H2S) |
Corrosion |
Chlorination |
Silica (SiO2) |
Scale in boilers and cooling water systems |
Lime softening |
Boiler Water Treatment chemicals manufacturer and supplier in India UAE Oman Nairobi, Sudan Yemen. One Shot Universal Liquid Treat is most advanced Boiler Water treatment Chemicals supplier in Mumbai, Navi Mumbai MIDC, Kolkata, Chennai, Haldia, Ennore, Paradip, Kandla Mundra Gandhidham, Visakhapatnam, Gangavaram, Kakinda, And in GULF Fuajirah, Dubai, Sharjah, Ajman, Abudhabi, UAE, Ruwi Barka Ghala, Muscat Oman, Nairobi Kenya, Sudan, Yemen