Corrosion Inhibitor Cool Water Treat

Organic liquid corrosion inhibitor with low-toxic poerty provides long-life corrosion protection for closed cooling water systems . Rxsol Cool water treat will protect all commonly used materials in engine cooling water systems, including aluminium.
Part number
RXSOL-81-6643-999
Generic name
Nitrite Based corrosion inhibitor
Active matter
45-50
Brand
RXSOL
Corrosion Inhibitor Cool Water Treat

Overview

Corrosion Inhibitor Cool water Treat is specialized Cooling Water treatment chemicals for a re-circulating water system.  Nitrite Based corrosion inhibitor Suitable for all types  water circulation cooling. 

Technical specifications

PHYSICAL AND CHEMICAL PROPERTIES

- PHYSICAL STATELIQUID
- ODOURMILD
- PH12.5 13.5
- FREEZING POINT< - 10 °C
- INITIAL BOILING POINT> 100 °C
- SOLUBILITY IN WATERCOMPLETE
- COLORPINK

Applications

Liquid product, easy to use. Environmentally friendly, fully organic product, low toxicity. Effective against cavitation and erosion. Superior heat transfer properties. Compatible with hoses, gaskets and seals. Compatible with glycols for frost protection. Stable product - non-depleting. The product can be used for corrosion inhibition in many types of closed re-circulation system such as: - Diesel engine cooling water systems - Compressor cooling water systems - Centralised cooling systems - Hot water heating systems - Auxiliary machinery cooling systems.

Corrosion Inhibitor Cool WATER Treat is an organic liquid corrosion inhibitor with low-toxic property provides long-life corrosion protection for closed cooling water systems RXSOL Cool WATER treat will protect all commonly used materials in engine cooling water systems, including aluminium. Cool WATER treat  does not contain components subject to rapid depletion. Cool WATER treat  is stable and  biodegradable

Dosage and directions

Using Method : -

Corrosion Inhibitor Cool water Treat  is a highly effective corrosion inhibitor for all common metals in cooling water systems.Where most traditional inhibitors react with the metal surface and form oxides that prevent further corrosion, Cool water treat  applies a thin and durable layer of protective molecules to the metal surfaces. This technology prevents the continuous build-up of insulating layers on heat transfer surfaces.

For new builds, RXSOL  recommends cleaning of the water system before commercing service. The system will always contain small amounts of oil and iron oxides, and this can be easly removed in 1 time with Rxsol Commissioning Cleaner. If the system is corroded or is more heavily contaminated use Rxsol Degreaser HD. RXSOL Safe Acid  for removal of metal oxides or scale is recommended.
For systems previously treated with other products, RXSOL recommend to drain and flush the system before refilling with distilled water and Cool WATER treat . The system should be clean and free from scale and corrosion products when starting the treatment.
The use of antifreeze is sometimes required if the vessel is to be laid up in cold areas, Cool water treat  can be used in conjunction with glycols for frost protection. If used in conjunction with glycols, It is recommended to increase the product concentration to 8%.

Dosing method
Cool water treat  should be dosed to a suitable point in the system. If the expansion tank is used, adequate circulation must be assured.
Dosage and control
Cool water treat  should always be present in a concentration of 5% or higher in the system. It is good practice to start with initial dose for an untreated system of 60 litres of Cool WATER treat /ton. 5% will provide sufficient protection of the system for a period of two to five years under normal conditions provided. To prevent residual falling below minimum level due to loss of cooling water, RXSOL recommend to maintain a level of 6% Cool WATER treat  in the cooling system.
The engine manufacturer's recommendations for water quality should always be complied with. Cool water treat  provides good protection even with contamination of the system by i.e. inorganc salts. Maintain Chloride levels and other contaminants at a minimum level. Most engine manufacturers recommend a maximum of 50 ppm Chlorides.

Characteristics and notes

CHEMICAL,PROCESS, CORROSION INHIBITOR, LIQUID KG
COMPOSITION / INFORMATION ON INGREDIENTS:

- AN AQUEOUS SOLUTION OF SODIUM NITRITE

- Content : SODIUM NITRITE 

- CAS # 7632-00-0

 

WHERE USED:

- RR WEST UNITS

- CBDC UNIT U-2026: USED IN FRESH COOLING WATER SYSTEM (U-2026) OF CBDC TO  PROTECT CARBON STEEL AS WELL AS YELLOW METALLURGY OF FCW COOLERS. FROM CORROSION AND CONTAINS PH BUFFERS TO DEFEND THE SYSTEM AGAINST PH CHANGES.

 

NOTE :

- SHELF LIFE REQUIRED IS 2 YEARS (MINIMUM) FROM DATE OF PRODUCTION 

Item Specs:

GENERIC TYPE: CORROSION INHIBITOR

FORM: LIQUID

SERVICE: WATER TREATMENT

 

Safety and SDS

Read the safety data sheet before handling. Wear suitable gloves and eye protection.

View safety data sheet
Product Name RXSOL-81-6643-999
Product Type Corrosion Inhibitor Cool WATER Treatment

Company Details:

RX MARINE INTERNATIONAL
105, A wing , BSEL , TECH PARK.
VASHI ,NEW BOMBAY 400703 INDIA

Stock Point : Mumbai, Kandla, Chennai, Vizag, Kolkata, Fujairah, Muscat

Phone +91 22 27815540 / 41 / 42
Fax +91 22 2781 1318 :::AOH :0091 9821214367
Email rxsolchemicals@gmail.com

Chemical Name

Concentration

CAS Number

EC Number

R Phrases*

Symbols Disodium

Sodium Nitrite and organics based corrosion inhibitor 45 - 54 Blend Blending Mixture --- ---

2-Sodium salt Tolyltriazole

1-3

29385-43-1

29385-43-1

22

Xn

Non Classified Proprietory ingredients

45 - 54

 

*See Section 16

Odour

 odourless

Appearance

Liquid, Pink, Soluble in water

Contact with eyes

Causes redness and irritation

Contact with skin

In cases of severe exposure, severe irritation may develop

Inhalation

Vapours or aerosols may cause irritation of eyes, nose and respiratory tract

Ingestion

The ingestion of significant quantities may cause gastro-intestinal disturbances

Skin Contact

Wash affected area with plenty of soap and water

EyesContact

If substance has got into eyes, immediately wash out with plenty of water for at least 15 minutes

Ingestion

  1. Never give anything by mouth to an unconscious person
  2. Do not induce vomiting

Inhalation

  1. is unlikely to occur
  2. Remove patient to fresh air
  3. Seek medical attention if ill effects occur

General

In case of accident or if you feel unwell, seek medical advice immediately (show the label where possible) (S45)

Fire-fighting measures

  1. Non combustible
  2. Nitrogen and carbon oxides may be formed
  3. Not flammable. In case of fire use extinguishing media appropriate to surrounding conditions

Personal Precautions

Wear protective clothing as per section 8

Environmental Precautions

Do not allow to enter public sewers and watercourses

Clean Up Actions

  1. Absorb spillage in inert material and shovel up
  2. Flush spill area with copious amounts of water

Handling

- Wear protective clothing as per section 8

- Avoid contact with skin and eyes (S24/25)

- Eyewash bottles should be available

Storage

- Keep in a cool, dry, well ventilated place

- Protect from frost

- Protect from heat

Exposure Limits

There are no recommended or established controls for this product

Exposure controls

The undiluted product must not be used in a confined space without good ventilation

Occupational exposure controls

- No respiratory protection is required unless subject to contact with substance mist

- Wear suitable protective clothing, including eye/face protection and gloves (plastic or rubber are recommended)

                                  

        Gloves              Goggles                 Suit               No_Smoking 

Odour

Odourless

Appearance

Liquid, Colourless to Pale Straw, soluble in water

pH

12.5 to 13.5  at 100 % concentration

Vapour pressure

not known

Freezing point

<0 °C to 760 °C

Relative Density  1.27 to 1.30

- This article is considered stable under normal conditions

- Avoid overheating, Keep away from frost

- Incompatible with strong oxidizing substances, Contact with acids liberates toxic gas (R31)

- See Section 5

Toxicological information

- Possible risk of harm to the unborn child (R63)

- In cases of severe exposure, redness and irritation may develop

- The ingestion of significant quantities may cause nausea/vomiting

Contact with skin

In cases of severe exposure, severe irritation may develop

Contact with eyes

Causes redness and irritation

Ingestion

- The ingestion of significant quantities may cause gastro-intestinal disturbances

- May cause nausea/vomiting

Carcinogenicity

No evidence of carcinogenic effects

Ecotoxicit

On available data, substance is not harmful to aquatic life

Mobility

Completely soluble in water

Persistence and Biodegradability

The components in this product are readily biodegradable

Bioaccumulation Potential

Bioaccumulation of the components in this product is insignificant.

- Do not discharge into drains or the environment, dispose to an authorised waste collection point

- Disposal should be in accordance with local, state or national legislation

- Not classified as hazardous for transport

Risk Phrases

Possible risk of harm to the unborn child (R63)

Safety Phrases Irritant

- Wear suitable gloves and eye/face protection (S37/39)

- If swallowed seek medical advice immediately and show this container or label (S46)

Text of R and S phrase codes used in this safety data sheet:- R34: Causes burns; R36: Irritating to eyes; R37: Irritating to respiratory system; R41: Risk of serious damage to eyes. The information provided about the product on this Safety Data Sheet has been compiled from knowledge of the individual constituents The data given here is based on current knowledge and experience. This Safety Data Sheet describes the product in terms of safety requirements and does not signify any warranty with regard to the product's properties The data given here only applies when product used for proper application(s). The product is not sold as suitable for other applications - usage in such may cause risks not mentioned in this sheet. Do not use for other application(s) without seeking advice from manufacturer

DISCLAIMER OF LIABILITY :The information in this SDS was obtained from sources which we believe are reliable. However, the information is provided without any warranty, express or implied, regarding its correctness. The conditions or methods of handling, storage, use or disposal of the product are beyond our control and may be beyond our knowledge. For this and other reasons, we do not assume responsibility and expressly disclaim liability for loss, damage or expense arising out of or in any way connected with the handling, storage, use or disposal of the product. This MSDS was prepared and is to be used only for this product. If the product is used as a component in another product, this MSDS information may not be applicable..

Request the signed SDS as PDF

Technical bulletin

Open technical bulletin

Description


RXSOL-81-6643-999 is a superior multifunctional, nitrite-based and triazole based chemical treatment used for the control of corrosion in closed cooling systems and chilled water systems. RXSOL-81-6643-999 is a liquid product containing a combination of ferrous and non-ferrous corrosion inhibitors, a non-carbonate buffer, scale inhibitors, dispersants and a leak detection dye.

Note: The stable oxide film that is formed by RXSOL-81-6643-999 prevents corrosion caused by electrolytic action between dis -similar metals used in the system.RXSOL-40-4011 has been field tested and found to have no detrimental effects on non metallic substances such as seals, glands,packing,hoses, gaskets etc., normally used in these’systems.



Application for DG-Sets


Internal combustionengines closed circuit cooling system compressor cooling system.RXSOL-81-6643-999 incorporates superior corrosion inhibitors to prevent corrosion works by free of scale deposits.

Advantages


Prolong the life of equipment by keeping scale and corrosion free. Since RXSOL-81-6643-999 is alkaline and so will suppress acid corrosion, which would otherwise result in corrosion damage such as pitting. However, the alkalinity control  is such that even if the product is accidentally overdosed, the pH of the water will remain within limits. The  metals which would be affected by extremes of alkalinity or acidity are protected

  • Improves generating cooling efficiency by maintaining a clean heat transfer
  • Reduced maintenance and down   time
  • Compatible with Coolants / Antifreeze solution / Glycol .
  • Friendly with   Metals (Like steel, Copper, Aluminum, all alloys) & Non-metal (Rubber, Hoses, Gasket etc.)

Note: In cases where systems are contaminated with oil and/or scale they should be cleaned before starting to apply RXSOL-81-6643-999.There are suitable RX BRAND products to carry out the cleaning. Degreasing should be carried out using RXSOL-10-1005-OB and descaling by using RXSOL-11-1008-DC

Method Of  Use


  1. Properly   clean  the  system  with  water  and  alkaline  liquid ,  if  necessary.
  2. The recommended dosage of RXSOL-81-6643-999 is 15.6-23.4 l/m3 of system capacity or 60.6-87 RXSOL-81-6643-999 of system capacity in all systems. Clean up the system if the system becomes contaminated with iron. Maintain 600-750 ppm nitrite as NO2. RXSOL-40-4011-020  is intended for industrial use only. It should not be fed to potable water systems
  3. When the product is dosed as recommended  limit By buffering action of RXSOL-81-6643-999 ,pH should be maintained between 8.3 and 10 by the treatment.
Note: Initial dosage for an untreated system is 9 litres of RXSOL-81-6643-999 /1000 litres of untreated distilled water.This will bring the treatment up to the minimum level of 1000 ppm nitrite.For best  result and  prolonged  engine life add  RXSOL-81-6643-999  every  500 -6500  km. or  250  to  300 hours  of  running  time  or  every  2 month   interval.

         

Specification


Color Clear  
pH Alkaline  
Odour None.  
Freezing  Point 17 0 c 
Nitrite (as PPM NO2) 0 100-200 300-600    700 -900 1100-1300 1440-2400
RXSOL-81-6643-999 / 1000L 13.0 11.3 8-10 5-7 1.5-3.5 0

Another variant of RXSOL-81-6643-999 is available with a colour indicator which makes it easy to identify if the corrosion inhibitor is used up or still active.

Handling: RXSOL-81-6643-999 is an alkaline product &should be handled like other chemical Avoid contact with Eyes,Skin,in case of contact,wash with copious amounts of water  immediately.

Availability

Corrosion Inhibitor Cool Water Treat chemicals manufacturer and supplier in Mumbai, MIDC, GIDC, Hazira Surat, Kolkata, Haldia, Fujairah, Dubai, Ajman, Sharjah, Abudhabi, Barka, Ruwi, Muscat Oman, Nairobi, Kenya, Sudan, Yemen

Our stock points and branches