RXSOL CHEMO PHARMA International Navi Mumbai, India

Products

7,071 products across 89 categories for marine, industrial, water treatment and laboratory use.

Browse all products Product catalogue

Boiler water treatment programme

Instead of buying four chemicals separately, a plant or vessel can ask RXSOL for a programme: we take the feed-water analysis and boiler data, select the products, calculate the initial and daily doses, supply the test kit and set the control ranges.

Steps

  1. You send feed-water hardness, alkalinity, chlorides, pH, boiler pressure, steaming rate and blowdown practice.
  2. We propose the programme — typically an oxygen scavenger (carbohydrazide, sulphite or hydrazine), an alkalinity/phosphate treatment (BoilerGuard SCP or Autotreat for small boilers), and a neutralising amine (Condensnol) — with doses per tonne of feed water.
  3. Chemicals, test kit and a log sheet are delivered; the crew or operator tests daily and adjusts within the stated ranges.
  4. We review the log monthly and adjust the programme.

Typical control ranges — P-alkalinity 100–300 ppm as CaCO3, sulphite reserve 20–50 ppm, chlorides below the boiler-maker's limit, condensate pH 8.3–9.0.

Frequently asked questions

Is this for marine or land boilers?

Both — auxiliary and exhaust-gas boilers on ships, fire-tube and water-tube boilers in plants.

What does the programme cost?

Only the chemicals and kits; the dosing plan is free with supply.

Can you supply hydrazine-free products?

Yes — carbohydrazide and sulphite-based scavengers.