Buffer Cleaner
Oman Chemical is leading one Largest Supplier, Manufacture a
|
Our regular customer of morpholine getting advantage of our pure imported morpholine as per there customized packing and requirements.
PRODUCT NAME | : | CYCLO HEXYL AMINE |
CAS number | : | 108-94-1 |
UN number | : | 1915 |
Formula | : | C6H10O |
Odour | : | ACETONE LIKE |
Soluble in water | : | SLIGHT |
Density | : | 0.948 at oC |
Boiling point | : | 156 oC |
Melting point | : | -31oC |
Viscosity | : | |
Flashpoint | : | 54 oC |
Explosive limits | : | 1.1 – 9.4 Vol% |
Vapour pressure | : | 4.7 mbar at 20 oC |
Skin absorption/irritation | : | YES |
TLV Country NL Year 1995 | : | 50 ppm 200 mg/m3 |
Pollution category 1994 | : |
D |
Symptoms. irritation eyes, skin, mucous membrane, respiratory system; eye, skin burns; skin sensitization; cough, pulmonary edema; drowsiness, dizziness.
Product Specifications: | |
Density |
1 |
Packing, Type |
PLASTIC |
Volume |
25 l |
pH |
10.5 |
Colour |
LIGHT YELLOW |
Appearance |
LIQUID |
Directions for use
This product is formulated for use in conjunction.Oxygen Scavenger Plus can be used in any boiler system, and in conjunction with mechanical deaeration systems. Removal of dissolved oxygen is vital for prevention of corrosion and especially pitting corrosion in boilers. When dosed into a boiler system, Oxygen Scavenger Plus will react with dissolved oxygen and form non corrosive compounds. The product is volatile, and left over product from oxygen scavenging in the pre-boiler section will evaporate and assist protection of the steam and condensate system. No solid materials are produced when using Oxygen Scavenger Plus.
Dosing method
Rx Marine International recommends continuously into the boiler feed line and Boiler Water Treatment Dosing Unit.
Dosing should be controlled so that the DEHA residual in the condensate is between 0.08-0,30 ppm. The consumption will depend on feed water temperature and the amount of water fed into the boiler. For more information about initial dosage and dose rate please consult your nearest Customer Centre.
Test result condensate PPM DEHA
0.00 - 0.08 0.08 - 0.30 0.30 +
Increase dose 25% Maintain dose Decrease dose 25%
Sampling and testing
A representative sample of Condensate should be drawn for analysis daily. The sample should always be taken from the same sampling point, cooled and tested immediately By Rxsol Test Kit. It is important that regular testing is carried out, to ensure the correct level of treatment is maintained.
Features
• Fast acting, liquid oxygen scavenger.
• Safe and easy to use, low toxicity.
• Reduces corrosion of iron and copper, increasing system life and reliability.
• Neutralises acids occurring in condensate system.
• Volatile product, provides distribution and protection throughout the boiler system, economical in use.
• Suitable for use in conjunction with combined and co-ordinated treatment programmes.
• Organic product, no dissolved solids added.
• Simple test to determine treatment level.
The establishment of protective metal oxide lay-ers through the use of reducing agents (such as hydrazine, hydroquinone, and other oxygen scavengers) is known as metal passivation or metal conditioning. Although "metal passivation" refers to the direct reaction of the compound with the metal oxide and "metal conditioning" more broadly refers to the promotion of a protective surface, the two terms are frequently used interchangeably.
The reaction of hydrazine and hydroquinone, which leads to the passivation of iron-based metals, proceeds according to the following reactions:
N2H4 | + | 6Fe2O3 | ® | 4Fe3O4 | + | 2H2O | + | N2 |
hydrazine | hematite | magnetite | water | nitrogen |
C6H4(OH)2 | + | 3Fe2O3 | ® | 2Fe3O4 | + | C6H4O2 | + | H2O |
hydroquinone | hematite | magnetite | benzoquinone | water |
Similar reactions occur with copper-based metals:
N2H4 | + | 4CuO | ® | 2Cu2O | + | 2H2O | + | N2 |
hydrazine | cupric oxide | cuprous oxide | water | nitrogen |
C6H6O2 | + | 2CuO | ® | Cu2O | + | C6H4O2 | + | H2O |
hydroquinone | cupric oxide | cuprous oxide | benzoquinone | water |
Magnetite and cuprous oxide form protective films on the metal surface. Because these oxides are formed under reducing conditions, removal of the dissolved oxygen from boiler feedwater and condensate promotes their formation. The effective application of oxygen scavengers indirectly leads to passivated metal surfaces and less metal oxide transport to the boiler whether or not the scavenger reacts directly with the metal surface.
Function Mechanism: -
Alkalinity Control | This components of RXSOL-50-5004-020 chemically precipitate the hardness of salts like Calcium & Magnesium & neutralizes the acidic conditions. |
Hardness Control | RXSOL-50-5004-020 provides phosphate reserve to effectively react with and precipitate the hardness salts introduces with the feed water. |
Sludge Conditioner | RXSOL-50-5004-020 component will preventing the sludge from adhering to metals surfaces. Boiler sludge can only be removed by blow down. |
Oxygen Scavangers | Catalyzed of RXSOL-50-5004-020 controls the formation of oxygen to protects boiler & steam line corrosion protection. As an additional benefits it will assist to neutralize dissolved carbon dioxide. In this way RXSOL-50-5004-020 preventing oxygen “Pitting” corrosion. |
RXSOL-50-5004-020 is dependent on boiler operating condition, Feed 200 gm to 1 Kg of RXSOL-50-5004-020 solution for per thousand Ltr of boilers water Then control the system by Periodic Alkalinity test procedure. FREE LOGSHEET is available for our registered member. ( Maintaining of Logsheet allow to observing and evaluating the test results trend in order to use the exact amount needed for the stabilization of the system
If p-Alkalinity is below 200 ppm increase the ratio of RXSOL-50-5004-020 solution. If p-Alkalinity is above 400 ppm reduce the concentration of RXSOL-50-5004-020 solution by dilution with water.
RXSOL ALKALINITY, PHOSPHTE and SULFITE TEST KITS are available on request.
USES PROCEDURE : Always dissolve powder before feeding in BOILER WATER TANK.
Control Procedure:-
Control is by simple boiler water tests or RX CLEANSERS can provide a suitable test kits for this purpose
PHYSICAL PROPERTIES BOILER SLUDGE CONDITIONER is a white high molecular weight solution. It is hydrophilic and of low causticity.
Appearance / Color : CLEAR liquid
pH : 8 Odor : Odorless
Form | Liquid |
Colour | Clear |
Density | 1.24 kg/lit |
pH | 8.5 - 10.0 |
Freezing Point | <1C |
Appearance | Colourless to brown hazy |
Odor | Odorless |
Flammability | Non Flammable |
pH | 5-9 |
Density | 1.1 |
Solubility | Completely soluble |
We carry a complete line of condensate treatment chemicals. Condensate treatment chemicals are used to increase the condensate pH, thus reducing corrosion to the entire boiler steam system. The most common product is a tri-blend amine of cyclohexylamine, morpholine, and diethylaminoethanol (DEAE) neutralizing amines, although we do have standard RXSOL products or we can custom blend to your needs.
RXSOL-50-5005-DCM1 10% DEAE, 10% Cyclo, 10% Morpholine
RXSOL-50-5005-DCM2 20% DEAE, 20% Cyclo, 20% Morpholine
RXSOL-50-5005-C 20% Cyclohexylamine
RXSOL-50-5005-D 20% DEAE
RXSOL-50-5005-M 20% Morpholine
RXSOL-50-5005-C5 50% Cyclohexylamine
RXSOL-50-5005-D 50% DEAE
RXSOL-50-5005-M5 50% Morpholine
RXSOL-50-5005-025 alkaline and the vapors are irritating to eyes and lungs. Avoid contact with eyes and skin. Do not take internally. Observe safety regulations wear Goggles, PVC gloves and Apron when handling Provide ample ventilation Avoid contact with skin in case of contacts wash with cupious amount of water immediately. If eyes are splashed give immediate and prolonged irrigation with clean running water and obtain medical attention.